Whether you’re hiring a licensed electrician or trying to DIY (with permits!), here’s what the Ontario Electrical Safety Code (OESC 2021) says you must follow for a safe, code-compliant installation.
Disclaimer:
These codes were selected based on a theoretical main floor rewire and do NOT represent a complete list. Additional codes may apply. Always consult the Ontario Electrical Safety Code and obtain proper permits and inspections to ensure a code-compliant installation. Fireline Electric always recommends hiring a Licensed Electrical Contractor (LEC) for any electrical work in your home.
What the Code Says
🔌 GENERAL WIRING REQUIREMENTS
- Use NMD90 (a.k.a. “Romex”) for all interior, dry-location residential wiring.
- Secure cables within 12” (300mm) of boxes and every 5 ft (1.5m) of framing (Rule 12-510).
- No horizontal drilling in notched studs unless properly protected with steel plates (Rule 12-516).
- Run wires neatly, not stapled too tight, not looped loosely, and keep them out of harm’s way (Rule 2-100, workmanship).
- Concealed splices are a hard no. All splices must be inside a box with a cover plate and remain accessible (Rule 12-3034).
- Cables must be protected 1.5″ from the surface of studs or protected with metal plates (Rule 12-516).
- Cables entering metal boxes must have grommets or connectors to prevent abrasion (Rule 12-3022).
- Aluminum wiring must only be handled by licensed electricians trained in its use (Rule 12-112).
🔲 RECEPTACLE OUTLET SPACING & RULES
Don’t skip this — these are among the most enforced rules during ESA inspections:
- Every wall 3 ft (900mm) or wider must have an outlet.
- No point along a wall can be more than 6 ft (1.8m) from a receptacle (Rule 26-720).
- Hallways longer than 10 ft (3m) require at least one outlet (Rule 26-710).
- Kitchen counters require a receptacle every 3 ft, and one within 1 ft (300mm) of the edge of the sink (Rule 26-712).
- Countertop plugs must not be more than 20” (500mm) above the counter unless physically impossible (backsplash, window, etc.).
- Islands and peninsulas must have at least one outlet (Rule 26-712).
- Receptacles cannot face upward on countertops unless inside a pop-up or appliance (Rule 26-712).
- Bathroom outlets must be within 3 ft (900mm) of the sink and GFCI protected (Rule 26-710 & 26-704).
- Outdoor outlets must be GFCI and weatherproof, even if covered (Rule 26-702 & 26-704).
- AFCI protection is required on all 120V receptacles in finished areas like bedrooms, living rooms, dining rooms, and hallways (Rule 26-724).
⚠️ PROTECTION DEVICES: GFCI & AFCI
- GFCI = Ground Fault Circuit Interrupter – Use in: Bathrooms, kitchens (within 1.5m of sink), unfinished basements, garages, outdoors, and laundry.
- AFCI = Arc Fault Circuit Interrupter – Required on all finished living space circuits, even if they only feed lighting (Rule 26-724).
Some circuits need both (e.g. bedroom outlets near a sink = GFCI/AFCI combo).
💡 LIGHTING CIRCUITS
- Every room must have at least one lighting outlet controlled by a switch (Rule 30-502).
- Stairs require 3-way switching if there’s a light and the stairs are over 4 steps (Rule 30-500).
- Closet lights must be enclosed and kept clear of shelving:
- Minimum 300mm (12″) clearance for incandescent
- 150mm (6″) for LED or fluorescent (Rule 30-308).
Bathroom fans with lights must be rated for damp or wet location use and connected to a dedicated switch if required.
🧰 BOXES & CONNECTIONS
- Boxes must be securely mounted and flush with drywall unless using extension rings (Rule 12-3012).
- All connections must use approved wire connectors (marettes) or pressure terminals (Rule 12-3034).
- Choose appropriately sized boxes. You cant overfill them. Every conductor, ground, and device counts toward box fill (12-3034)
⚙️ CIRCUIT DESIGN & PANEL RULES
- Max 12 outlets (lights + plugs) per 15A circuit unless calculated load permits more (Rule 8-104).
- Label each circuit clearly in the panel (Rule 2-100).
- Working clearance in front of panel: 1m (39″) (Rule 2-308).
- Don’t stack too many breakers on one bus — check panel max for tandem breakers.
🛠️ DEDICATED CIRCUITS YOU CAN’T SKIP
- Kitchen counter plugs → 2 x 20A circuits minimum (Rule 26-654).
- Microwave, dishwasher, fridge, and gas stove ignitor → separate circuits preferred.
- Laundry outlet → 20A dedicated circuit (Rule 26-722).
- Bathroom plug → 20A GFCI on its own breaker (Rule 26-724).
- Electric baseboard heaters → each one requires its own properly sized breaker and wire (Rule 62-104).
🌎 BONDING & GROUNDING
- Bond all metal boxes, fixtures, and devices using the ground screw or pigtail (Rule 10-606).
- Use green or bare copper conductors for grounding only (Rule 10-602).
- Ground wires must be twisted together with a pigtail to the device or box (Rule 10-814).
📋 PERMITS & INSPECTIONS
- ESA Permit = Mandatory before you touch a wire.
- You must schedule an inspection at the rough-in and finish.
- Homeowners can only do this work on their own primary residence, not rentals or flips.
Understanding these key code requirements is the first step toward a safe and compliant rewire. Always make sure you’ve pulled the proper permits, and when in doubt, consult a licensed electrician or the Ontario Electrical Safety Code directly.